DS 2.501A 4 - 16 03/03
IAC BASE UNITS ON A LAN (NO TOUCH-SCREENS)
IAC TOUCH SCREENS AND BASE UNITS ON A LAN
LAN from
PC or MIU
Fig.2
LAN B should be screened with the screen earthed only on a verified earth at the computer or MIU.
† LAN A and B screens should be connected to the isolated Ground Terminals of each of the IACs on
the LAN - see Fig.3A.
Upto 31 Networking Controllers and 1000m, more (upto 31 controllers and 1000m
if an MIU is used as a Repeater)
DETAIL OF LAN SCREENING
Fig.3A
ISOLATED
GROUND
ISOLATED
GROUND
More IACs
*The number of IAC controllers on a Touch-screen
Sub LAN is limited to 32 base units including the one
the Touch-screen is plugged into. Each Touch-screen
can display upto 256 parameters.
Controllers (including MIUs) on the main LAN and sub-LAN must not
have conflicting addresses.
Controllers on different sub-LANs may use the same address. Ideally the sub-LAN addresses
should be kept within a range so as not to use up all of the main LAN addresse
s.
LAN B should be screened with the screen earthed only on a verified good earth at the computer or MIU.
† LAN A and B screens should be connected to the isolated Ground Terminals of each of the IACs on the
LAN - see Fig.8.
Fig.3
Upto 31*, MMC3701, IAC400/600s and 1000m
To further
Networking
controllers
(Address range 1 to
63, MIU required if
total number is
greater than 31)
Touch
screen
addresses
65 to 95.
Up to 31
Touch
screens
Page view 3