Multitech MT1932ZDXK User Manual Page 13

  • Download
  • Add to my manuals
  • Print
  • Page
    / 16
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 12
03/03 13 - 16 DS 2.501A
Example:- Set address 5.
When using a user defined preset (or customized preset) first make
sure that preset 0 is selected via the bit switch. The unit should then be
left with the address selected on the bit switches (bit switch 7 ON). This
ensure that should data corruption occur the controller will not attempt
to load any default values. As the application is user defined the
controller cannot know what would be suitable defaults. The preset
setting can be checked using Satchnet via the system module.
COLD STARTING CONTROLLERS
In order to cold start an IAC controller (i.e. clear out the configuration
data) the following procedure should be followed.
1. Disconnect all outputs from the plant.
2. Set bit switch 1 ON, all others OFF.
Toggle bit switch 8. This causes the controller to load preset
application 1.
3. Set all bit switches to OFF. Toggle bit switch 8. This causes the
controller to load preset 0 (no application).
4. If you are using preset 0 you should now set the controller address.
If you are using a hardware preset application set the application
number on bit switches 1 to 6 and ensure that bit switch 7 is set to
OFF.
5. Once the application number is set it must be entered into the IAC
by toggling bit switch 8.
6. If the IAC is not to be connected to a computer then it is not
necessary to set an address for it.
7. Set the controller address (if required) on bit switches 1 to 6 and
set bit switch 7 to ON.
8. Once the address has been set it must be entered in to the IAC by
toggling bit switch 8. The controller address is now loaded and the
IAC will communicate at 1200 bps.
9. Re-connect outputs to plant.
Note:
Whenever a firmware upgrade is performed the unit must be cold started.
CONTROLLER LED
Normal Operation
On both the IAC400 and IAC200 controllers the on board LED is under
software control and should, under normal operation, flash at a regular
interval. The rate of flash is directly proportional to the loading imposed
by the application the controller is running, i.e. the more modules you
use the slower the LED flashes.
Unit Initialization
Whenever the controller is powered up or reset the LED will initially
flash very quickly before adopting the standard flash rate. (Only applies
to VAV207, VAS207 and DDC 206 and later versions).
Data Corruption
If a controller appears to be continually performing unit initialization, it
is likely that data corruption has occurred. Toggle bit switch 8 to reload
defaults. Download the configuration from Satchnet if it is a software
preset.
SECTION 6 –SATCHNET COMMUNICATION
TROUBLE SHOOTING
This section gives guidelines for interpreting the communications
failure percentage displayed on Satchnet. It is not intended that this will
provide an answer to every problem but providing that the Satchnet
wiring recommendations are followed (Section 1) it should be possible
to diagnose most communication problems.
Before any analysis of possible problems can be performed, it is
necessary to get all controllers on an "even playing field" from the
Satchnet point of view. Ideally a duplicate copy of Satchnet should be
installed in a separate directory. Controllers should then be created but
no parameters extracted from them. Ideally all controllers should be
placed on the same Satchnet screen but if this is not possible group
them according to location. If possible all controllers should be running
the same application or no application. By following this procedure you
ensure that the polling of the controllers is evenly spread and thereby
make the communication failures statistic comparable between
controllers.
To view the failure percentage of a controller you must click on the
controller with the RIGHT button. The following window is displayed.
The operation of the failure statistic is influenced by many things such
as:
Protocol used,
Satchnet polling used,
Relative controller transceiver transmitter strengths,
Location of failing controller.
The precise nature of the failure percentage and how one failing
controller affects another is therefore site specific. However, some
general trends have been noted.
A failure percentage of 0-10% does not generally have a detrimental
effect on system performance. Some messages may fail but are
automatically re-tried by Satchnet. Where MIUs and IAC
touch-screens are used, there may be a slight increase in failure
percentage of 2-3% due to the message buffering these products
introduce.
Where two controllers have been given the same address the failure
percentage of that address will typically range from 40-90%. Other
working controllers will be affected and their failure percentages will
typically range from 10-30%.
Where a controller or group of controllers have a 100% failure rate,
suspect either addressing, wiring or hardware faults.
In general when tracing communications problems always start with
the unit with the highest failure rate. Isolation of this unit may well
improve the failure rates of the other controllers. The LAN may be split
up to help locate the fault.
GROUP ADDRESSING
The IAC200/400/600 may belong to 10 groups. The IAC200/400/ 600
will accept a group message if the message group address matches
any one of programmed group addresses.
Do not mix different controller types on the same group address. This
will result in corruption of the slave controller.
Set switch 7 to ON
Set address 5, set
switches 1 and 3 ON.
Set switch 8 to ON
Set switch 8 to OFF
This procedure will enter
the address into the
controller memory.
Page view 12
1 2 ... 8 9 10 11 12 13 14 15 16

Comments to this Manuals

No comments