Chapter 3 - AsconControlLib
101
3-3-5 S2_TFUZZY
FB Prototype
S2_TFUZZY
Input parameters
Output parameters
Description
This function block is able to perform a tuning calculation selecting the best method
according to the process conditions. The possible algorithms are the “
Step
Response
” or the “
Natural Frequency
” (please refer to the specific documentation),
and the FB selects the first if the PV is far from the setpoint more then 5% (at the
moment of the run command), or the second in the other cases. It works together a
P.I.D. block with which shares the inputs and the outputs from and for the process.
Input Type Description
ENABLE BOOL Function block enable
SP REAL Setpoint value [0…100.0]
MEAS REAL Measure value [0…100.0]
ACT_TYPE BOOL P.I.D. action type
OUTLO REAL Lo value for OUT output [0…100.0]
OUTHI REAL Hi value for OUT output [0…100.0]
Output Type Description
TOUT REAL Function block output [OUTLO…OUTHI]
TPB REAL Calculated proportional band [%]
TTI REAL Calculated integral time [s]
TTD REAL Calculated derivative time [s]
TDBMP BOOL Bumpless command for the P.I.D.
TRUNNING BOOL Running flag
TVALID BOOL Successful tuning calculation flag
ENABLE
SP
MEAS
ACT_TYPE
OUTLO
OUTHI
BOOL
REAL
REAL
BOOL
REAL
REAL
¡
¡
¡
¡
¡
¡
REAL
REAL
REAL
REAL
BOOL
BOOL
BOOL
TOUT
TPB
TTI
TTD
TDBMP
TRUNNING
TVALID
¡
¡
¡
¡
¡
¡
¡