1-3-41 SLOPE LIMIT
FB Prototype
SLOPE_LIMIT
Input parameters
Output parameters
Description
This function block limit the Output value rate of change in according to the speci-
fied
SL_UP
and
SL_DOWN
values.
Default values
Label Type Description
ENABLE BOOL Enable Slope Function
AI REAL Analog input value
SL_UP REAL Slope Up Analog Value
SL_DOWN REAL Slope Down Analog Value
Label Type Description
AOUT REAL Analog Output Value conditionated by the Slopes
ENABLE
AI
SL_UP
SL_DOWN
BOOL
REAL
REAL
REAL
¡
¡
¡
¡
REAL AOUT
¡
Input Default values
ENABLE
FALSE
AI
0.0
SL_UP
1.0
SL_DOWN
1.0
Output Default values
AOUT
0.0